What Percentage of ISO ePM1 Is Equivalent to MERV 13? Don’t Directly Convert Filter Ratings When Purchasing Filters

When purchasing industrial air filters, specifications may state “MERV 13,” while product information may indicate “ISO ePM1.” Since both figures appear to be related to filtration efficiency, can they be directly treated as equivalent?
For procurement and engineering personnel, this is not simply a matter of translating terminology. The real question is whether the proposed product can meet the original specification, required airflow, and HVAC equipment conditions.
Hencolin’s medium-efficiency synthetic-fiber box filter product page provides classification information based on the older EN 779 standard and ASHRAE 52.2. If the project owner has switched to specifying an ePM classification under ISO 16890, suppliers should be asked to provide the corresponding data for the specific model rather than directly converting the MERV value shown on the product page into a particular ePM percentage.
Outline
- What percentage of ISO ePM1 is equivalent to MERV 13?
- First, understand what the two classification systems measure
- MERV: Performance evaluated by particle-size ranges
- ISO 16890: Classification using ePM
- How should older EN 779 data be used?
- When comparing filter ratings, also compare airflow and pressure drop
- Five items that should be clearly specified in procurement documents
- Frequently Asked Questions
- Can online MERV/ePM comparison tables not be used at all?
- Is MERV 13 necessarily better than every ePM1 filter?
- If the efficiency rating is specified, do we still need to consider pressure drop?
What Percentage of ISO ePM1 Is Equivalent to MERV 13?
There is no single fixed conversion value that applies to all filters.
MERV is a classification method based on testing and rating under ASHRAE 52.2, while ISO 16890 classifies filters according to particulate matter removal efficiency, such as ePM1, ePM2.5, and ePM10. The testing and calculation methods used by the two standards are different.
A general comparison table may be useful for preliminary communication, but it cannot replace test results obtained for a specific filter according to the required standard. For formal procurement, compliance should be determined based on the project requirements and the corresponding documentation for the specific product.
First, Understand What the Two Classification Systems Measure
MERV: Performance Evaluated by Particle-Size Ranges
ASHRAE 52.2 evaluates the particle removal efficiency of general ventilation filters across different particle-size ranges. ASHRAE’s published information divides the relevant ranges into 0.3–1.0 µm, 1.0–3.0 µm, and 3.0–10 µm. The MERV rating is then determined according to the standard test method.
Therefore, MERV is a product classification obtained under a specified test method. It does not mean that a filter removes exactly the same percentage of particles across all particle sizes.
ISO 16890: Classification Using ePM
ISO 16890-1 establishes a classification system for air filters used in general ventilation based on particulate matter removal efficiency and specifies requirements for evaluation and labeling.
When a procurement specification states ePM1, ePM2.5, or ePM10, the efficiency percentage following the classification should also be reviewed together with the relevant test documentation. Simply stating “complies with ISO 16890” is not sufficient to define the filtration performance required by the project owner.
ISO also notes that laboratory results obtained according to the standard cannot, by themselves, be directly used to quantify or predict filtration efficiency and service life under actual operating conditions. Actual airflow, filter-to-frame sealing, dust loading, and maintenance conditions must also be managed separately.
How Should Older EN 779 Data Be Used?
Existing equipment and some product catalogs may still show classifications such as M5, M6, F7, and F8 under EN 779. These classifications can be useful for identifying historical procurement information or existing product data.
However, if a new project specifically requires ISO 16890 or ASHRAE 52.2, simply replacing the old classification name with a new classification should not be considered sufficient specification verification.
For example, Hencolin’s medium-efficiency synthetic-fiber box filter product page lists various EN 779 and MERV options. However, the product page does not therefore provide an ISO ePM test value for every option.
If the quotation requirement specifies a particular ISO ePM1 efficiency, procurement personnel should provide the complete requirement to Hencolin and ask the supplier to confirm the corresponding model and available documentation.
Do not independently assign an ePM value based on product color, an older classification, or an online comparison table.
When Comparing Filter Ratings, Also Compare Airflow and Pressure Drop
Even when two products use the same classification system, it is still necessary to verify whether the product is suitable for the actual AHU.
At a minimum, check:
- Actual frame dimensions and filter depth
- Rated airflow
- Initial pressure drop at the specified airflow
- The allowable resistance range of the equipment
Hencolin’s box-filter product information lists different dimensions and airflow capacities. When comparing products, these specifications should be matched to the selected model one by one.
The installation method should also not be overlooked. If gaps remain between the filter and the mounting frame, some air may bypass the filter media. Even if the filter media itself meets the required test rating, the actual filtration performance of the system may differ.
Therefore, when requesting a quotation, it is preferable to provide equipment-slot photos, frame configuration, and whether sealing materials are required, and then confirm the final delivery specifications.
Five Items That Should Be Clearly Specified in Procurement Documents
First, specify which standard and classification or efficiency value is required. Avoid using vague descriptions such as “high efficiency.”
Second, require the quotation to identify the exact corresponding model and confirm that the submitted documentation and delivered product are the same model.
Third, specify the actual dimensions, filter depth, rated airflow, and acceptable initial pressure drop.
Fourth, clearly state the requirements for the mounting frame, flange, and sealing.
Fifth, if the project requires test reports or acceptance documents, confirm the required document contents and delivery method during the quotation stage.
If existing equipment only has EN 779 or MERV records while the new specification uses ePM, procurement personnel can provide both the original filter information and the new project requirements to the supplier.
This allows the supplier to make recommendations based on the airflow and available space of the same equipment, while clearly indicating which performance characteristics are supported by documentation and which still require testing or confirmation.
Frequently Asked Questions
Can Online MERV/ePM Comparison Tables Not Be Used at All?
They can be used for a preliminary understanding of the general relationship between different classification systems. However, they should not be used as the sole proof that a specific product complies with a procurement specification.
Formal evaluation should still be based on the applicable test data for the specific model.
Is MERV 13 Necessarily Better Than Every ePM1 Filter?
No. First confirm the efficiency percentage following the ePM1 classification, the product’s test method, and the specified airflow. The product can then be evaluated according to the project requirements.
If the Efficiency Rating Is Specified, Do We Still Need to Consider Pressure Drop?
Yes. An efficiency classification cannot replace equipment compatibility evaluation. The resistance of the new filter at the design airflow and the actual installation conditions can both affect filter selection.
If your specification includes EN 779, MERV, and ISO ePM classifications at the same time, provide Hencolin with the original filter specification, equipment airflow, filter-slot dimensions, and required test documentation when requesting a quotation.
This will help confirm a suitable medium-efficiency synthetic-fiber box filter or other air-filter product without relying on an assumed direct conversion between different classification systems.